ANALISIS DROP TEGANGAN SEBELUM DAN SESUDAH PENAMBAHAN FEEDERBARU PADA JARINGAN TEGANGAN RENDAHDI PT.PLN (PERSERO) UP3 KEBON JERUK
ctrlnum |
55845 |
---|---|
fullrecord |
<?xml version="1.0"?>
<dc schemaLocation="http://www.openarchives.org/OAI/2.0/oai_dc/ http://www.openarchives.org/OAI/2.0/oai_dc.xsd"><relation>http://repository.mercubuana.ac.id/55845/</relation><title>ANALISIS DROP TEGANGAN SEBELUM DAN SESUDAH PENAMBAHAN FEEDERBARU PADA JARINGAN TEGANGAN RENDAHDI PT.PLN (PERSERO) UP3 KEBON JERUK</title><creator>SUJARWADI, TITO</creator><subject>005.754 Network Databases/Pangakalan Data Jaringan</subject><subject>530 Physics/Fisika</subject><subject>537 Electricity/Fisika Listrik</subject><subject>537.6 Electrodinamics, Electric Current/Elektrodinamik, Arus Listrik</subject><description>Electricity problems that are often felt by the community are the problem of voltage drop. One of the areas experiencing a voltage drop problem is the Aries Kencana residential area. Voltage drop on customers in this area exceeds 10% of the standards allowed by PLN (SPLN No.1 Year 1995). The measured voltage at 12.00 is 200 V and at night when the peak load at 19.00 is 180 V and occurs at the customer locationat the end of the Low Voltage Network. With very low voltageproblem, electrical equipment to customers and electronic devices will be damaged quickly. At 19:00 when a peak load occurs, consumers cannot turn on the TV, radio, refrigerator and other electronic devices.The method of adding a new feeder by dividing the load on the network side and transferring the network is an attempt to improve the voltage drop. This analysis is carried out by using technical data and measurements to obtain the results of service voltage quality according to standards and reduce the impact of voltage drop.From the results of the calculation analysis on SP 123 substation, the voltage drop that occurs in Aries Kencana residentiualis caused by a network that is too long, and the load accumulates on one feeder. The voltage drop obtained from the measurement before the addition of the feeder is 50 volts with a percentage of 21.7% exceeding the tolerance limit permitted by the SPLN. By adding a new network and carrying out a reduction of the calculated load of 37.66 Amperwill be able to press the voltage drop up to 6,3%. The voltage drop that occurs does not exceed the conditions required by the SPLNKeyword : Low Voltage Network, Voltage Drop, AddingNew Feeder

Permasalahan listrik yang sering dirasakan oleh masyarakat adalah masalah drop tegangan. Salah satu daerah yang mengalami masalah drop tegangan adalah daerah perumahan Aries Kencana. Droptegangan pada pelanggan di daerah ini melebihi 10% dari standar yang diperbolehkanPLN (SPLN No.1 Tahun 1995).Tegangan listrik yang terukur pada siang hari yaitu jam 12.00 adalah 200 V dan pada malam hari saat terjadi beban puncak jam 19.00 adalah 180 V dan terjadi pada lokasi pelanggan JTR paling ujung. Dengan tegangan yang sangat rendah maka peralatan–peralatan listrik pada pelanggan dan alat-alat elektronika akan menjadi cepat rusak. Pada jam 19:00 saat terjadi beban puncak, konsumen tidak bisa menyalakan TV, radio, kulkas dan alat elektronik lainnya.Metodepenambahan feederbaru dengan pembagian beban di sisi jaringandan pengalihan jaringan merupakan suatuupaya untuk memperbaiki droptegangan.Analisis ini dilakukan dengan menggunakan data-data teknik dan pengukuran untuk mendapatkan hasil kualitas tegangan pelayanan sesuai standar dan mengurangi dampak droptegangan.Dari hasil analisis perhitungan pada gardu SP 123,Drop tegangan yang terjadi di perumahan Aries Kencanadisebabkan olehjaringan terlalu panjang, dan beban yang menumpuk pada satu feeder. Drop tegangan yang diperoleh dari pengukuran sebelum dilakukannya penambahan feederadalah sebesar 50 volt dengan persentase 21,7 %melampaui batas toleransi yang diizinkan oleh SPLN. Dengan menambah jaringan baru dan melakukan pengurangan beban yang terhitung sebesar 37,66 A akan dapat menekan drop tegangan hingga 6,3%.Drop tegangan yang terjadi ini tidak melebihi ketentuan yang disyaratkan oleh SPLNKata Kunci: Jaringan Tegangan Rendah, DropTegangan, Penambahan Feeder</description><date>2020-05-18</date><type>Thesis:Thesis</type><type>PeerReview:NonPeerReviewed</type><type>Book:Book</type><language>ind</language><identifier>http://repository.mercubuana.ac.id/55845/1/1.HALAMAN%20JUDUL.pdf</identifier><type>Book:Book</type><language>ind</language><identifier>http://repository.mercubuana.ac.id/55845/2/5.ABSTRAK.pdf</identifier><type>Book:Book</type><language>ind</language><identifier>http://repository.mercubuana.ac.id/55845/3/2.LEMBAR%20PERNYATAAN.pdf</identifier><type>Book:Book</type><language>ind</language><identifier>http://repository.mercubuana.ac.id/55845/4/3.LEMBAR%20PENGESAHAN.pdf</identifier><type>Book:Book</type><language>ind</language><identifier>http://repository.mercubuana.ac.id/55845/5/4.KATA%20PENGANTAR.pdf</identifier><type>Book:Book</type><language>ind</language><identifier>http://repository.mercubuana.ac.id/55845/6/6.DAFTAR%20ISI.pdf</identifier><type>Book:Book</type><language>ind</language><identifier>http://repository.mercubuana.ac.id/55845/7/7.DAFTAR%20TABEL.pdf</identifier><type>Book:Book</type><language>ind</language><identifier>http://repository.mercubuana.ac.id/55845/8/8.DAFTAR%20GAMBAR.pdf</identifier><type>Book:Book</type><language>ind</language><identifier>http://repository.mercubuana.ac.id/55845/9/9.DAFTAR%20LAMPIRAN.pdf</identifier><type>Book:Book</type><language>ind</language><identifier>http://repository.mercubuana.ac.id/55845/10/10.BAB%20I.pdf</identifier><type>Book:Book</type><language>ind</language><identifier>http://repository.mercubuana.ac.id/55845/11/11.BAB%20II.pdf</identifier><type>Book:Book</type><language>ind</language><identifier>http://repository.mercubuana.ac.id/55845/12/12.BAB%20III.pdf</identifier><type>Book:Book</type><language>ind</language><identifier>http://repository.mercubuana.ac.id/55845/13/13.BAB%20IV.pdf</identifier><type>Book:Book</type><language>ind</language><identifier>http://repository.mercubuana.ac.id/55845/14/14.BAB%20V.pdf</identifier><type>Book:Book</type><language>ind</language><identifier>http://repository.mercubuana.ac.id/55845/15/15.DAFTAR%20PUSTAKA.pdf</identifier><type>Book:Book</type><language>ind</language><identifier>http://repository.mercubuana.ac.id/55845/16/16.LAMPIRAN.pdf</identifier><identifier> SUJARWADI, TITO (2020) ANALISIS DROP TEGANGAN SEBELUM DAN SESUDAH PENAMBAHAN FEEDERBARU PADA JARINGAN TEGANGAN RENDAHDI PT.PLN (PERSERO) UP3 KEBON JERUK. S1-Sarjana thesis, Universitas Mercu Buana Jakarta. </identifier><recordID>55845</recordID></dc>
|
language |
ind |
format |
Thesis:Thesis Thesis PeerReview:NonPeerReviewed PeerReview Book:Book Book |
author |
SUJARWADI, TITO |
title |
ANALISIS DROP TEGANGAN SEBELUM DAN SESUDAH PENAMBAHAN FEEDERBARU PADA JARINGAN TEGANGAN RENDAHDI PT.PLN (PERSERO) UP3 KEBON JERUK |
publishDate |
2020 |
topic |
005.754 Network Databases Pangakalan Data Jaringan 530 Physics Fisika 537 Electricity Fisika Listrik 537.6 Electrodinamics Electric Current/Elektrodinamik Arus Listrik |
url |
http://repository.mercubuana.ac.id/55845/1/1.HALAMAN%20JUDUL.pdf http://repository.mercubuana.ac.id/55845/2/5.ABSTRAK.pdf http://repository.mercubuana.ac.id/55845/3/2.LEMBAR%20PERNYATAAN.pdf http://repository.mercubuana.ac.id/55845/4/3.LEMBAR%20PENGESAHAN.pdf http://repository.mercubuana.ac.id/55845/5/4.KATA%20PENGANTAR.pdf http://repository.mercubuana.ac.id/55845/6/6.DAFTAR%20ISI.pdf http://repository.mercubuana.ac.id/55845/7/7.DAFTAR%20TABEL.pdf http://repository.mercubuana.ac.id/55845/8/8.DAFTAR%20GAMBAR.pdf http://repository.mercubuana.ac.id/55845/9/9.DAFTAR%20LAMPIRAN.pdf http://repository.mercubuana.ac.id/55845/10/10.BAB%20I.pdf http://repository.mercubuana.ac.id/55845/11/11.BAB%20II.pdf http://repository.mercubuana.ac.id/55845/12/12.BAB%20III.pdf http://repository.mercubuana.ac.id/55845/13/13.BAB%20IV.pdf http://repository.mercubuana.ac.id/55845/14/14.BAB%20V.pdf http://repository.mercubuana.ac.id/55845/15/15.DAFTAR%20PUSTAKA.pdf http://repository.mercubuana.ac.id/55845/16/16.LAMPIRAN.pdf http://repository.mercubuana.ac.id/55845/ |
contents |
Electricity problems that are often felt by the community are the problem of voltage drop. One of the areas experiencing a voltage drop problem is the Aries Kencana residential area. Voltage drop on customers in this area exceeds 10% of the standards allowed by PLN (SPLN No.1 Year 1995). The measured voltage at 12.00 is 200 V and at night when the peak load at 19.00 is 180 V and occurs at the customer locationat the end of the Low Voltage Network. With very low voltageproblem, electrical equipment to customers and electronic devices will be damaged quickly. At 19:00 when a peak load occurs, consumers cannot turn on the TV, radio, refrigerator and other electronic devices.The method of adding a new feeder by dividing the load on the network side and transferring the network is an attempt to improve the voltage drop. This analysis is carried out by using technical data and measurements to obtain the results of service voltage quality according to standards and reduce the impact of voltage drop.From the results of the calculation analysis on SP 123 substation, the voltage drop that occurs in Aries Kencana residentiualis caused by a network that is too long, and the load accumulates on one feeder. The voltage drop obtained from the measurement before the addition of the feeder is 50 volts with a percentage of 21.7% exceeding the tolerance limit permitted by the SPLN. By adding a new network and carrying out a reduction of the calculated load of 37.66 Amperwill be able to press the voltage drop up to 6,3%. The voltage drop that occurs does not exceed the conditions required by the SPLNKeyword : Low Voltage Network, Voltage Drop, AddingNew Feeder
Permasalahan listrik yang sering dirasakan oleh masyarakat adalah masalah drop tegangan. Salah satu daerah yang mengalami masalah drop tegangan adalah daerah perumahan Aries Kencana. Droptegangan pada pelanggan di daerah ini melebihi 10% dari standar yang diperbolehkanPLN (SPLN No.1 Tahun 1995).Tegangan listrik yang terukur pada siang hari yaitu jam 12.00 adalah 200 V dan pada malam hari saat terjadi beban puncak jam 19.00 adalah 180 V dan terjadi pada lokasi pelanggan JTR paling ujung. Dengan tegangan yang sangat rendah maka peralatan–peralatan listrik pada pelanggan dan alat-alat elektronika akan menjadi cepat rusak. Pada jam 19:00 saat terjadi beban puncak, konsumen tidak bisa menyalakan TV, radio, kulkas dan alat elektronik lainnya.Metodepenambahan feederbaru dengan pembagian beban di sisi jaringandan pengalihan jaringan merupakan suatuupaya untuk memperbaiki droptegangan.Analisis ini dilakukan dengan menggunakan data-data teknik dan pengukuran untuk mendapatkan hasil kualitas tegangan pelayanan sesuai standar dan mengurangi dampak droptegangan.Dari hasil analisis perhitungan pada gardu SP 123,Drop tegangan yang terjadi di perumahan Aries Kencanadisebabkan olehjaringan terlalu panjang, dan beban yang menumpuk pada satu feeder. Drop tegangan yang diperoleh dari pengukuran sebelum dilakukannya penambahan feederadalah sebesar 50 volt dengan persentase 21,7 %melampaui batas toleransi yang diizinkan oleh SPLN. Dengan menambah jaringan baru dan melakukan pengurangan beban yang terhitung sebesar 37,66 A akan dapat menekan drop tegangan hingga 6,3%.Drop tegangan yang terjadi ini tidak melebihi ketentuan yang disyaratkan oleh SPLNKata Kunci: Jaringan Tegangan Rendah, DropTegangan, Penambahan Feeder |
id |
IOS5909.55845 |
institution |
Universitas Mercu Buana |
institution_id |
134 |
institution_type |
library:university library |
library |
Perpustakaan Universitas Mercu Buana |
library_id |
542 |
collection |
Repository Universitas Mercu Buana |
repository_id |
5909 |
subject_area |
Econmics/Ilmu Ekonomi Communication/Komunikasi Engineering/Ilmu Teknik Measurement/Teknik Desain, Pengujian, Pengukuran, Kualitas, Perawatan, Pemeliharaan, Perbaikan |
city |
Jakarta Barat |
province |
DKI JAKARTA |
shared_to_ipusnas_str |
1 |
repoId |
IOS5909 |
first_indexed |
2020-05-26T03:14:53Z |
last_indexed |
2020-06-16T14:17:36Z |
recordtype |
dc |
_version_ |
1685794935738990592 |
score |
17.538404 |