OPTIMASI DIAMETER PIPA UTAMA PADA SISTEM JARINGAN PIPA DISTRIBUSI AIR BERSIH GEDUNG RUMAH SAKIT PENDIDIKAN UNIVERSITAS MUHAMMADIYAH MALANG MENGGUNAKAN PROGRAM LINEAR

Main Author: NINGSIH, ELIYARSIH WIDYA
Format: Thesis NonPeerReviewed
Terbitan: , 2011
Subjects:
Online Access: http://eprints.umm.ac.id/15180/
Daftar Isi:
  • Education Hospital of University of Muhammadiyah Malang is a construction with several building, some of them are main building consisted of 6 floor, accommodation development building, special unit building, guest house building and official housing for doctor. Water installation on facilities like hospital is an important part. Water installation plan in Education Hospital of University of Muhammadiyah Malang should be planned in details. So that there needed to do complete diameter analysis to reach proper pressure and debt. Linear program is one method used to solve optimizing problems. Linear program equation was Z min =( X11.C1 + X12.C2 + X13.C3 + X14.C4 + X15.C5) with constraint X11 + X12 + X13 + X14 + X15 and press residue in every tied J11.X11 + J12.X12 + J13.X13 + J14.X14 + J15.X15 Simulation result using linear programming found optimum diameter in pipe network. Optimum diameter of clear water distribution in Education Hospital of University of Muhammadiyah Malang pipe network were Building A: 5th floor, 4th floor, 3rd floor, 2nd floor using the pipe diameter of 4", 1st floor, basement floor using a pipe diameter of 2,5 '', in Building D and H, in building E and K is also using the pipe diameter of 4", in G building using pipe diameter 2.