OPTIMASI LOAD TAP CHANGER GUNA MEMINIMALISASI RUGI ALIRAN DAYA MENGGUNAKAN METODE PARTICLE SWARM OPTIMIZATION (Studi Kasus Pada PT Krakatau Daya Listrik)

Main Author: Wibowo, Bayu
Format: Thesis NonPeerReviewed Book
Bahasa: ind
Terbitan: , 2014
Subjects:
Online Access: https://eprints.untirta.ac.id/11362/1/OPTIMASI%20%20LOAD%20TAP%20CHANGER%20GUNA.pdf
https://eprints.untirta.ac.id/11362/
https://ft.untirta.ac.id
Daftar Isi:
  • PT Krakatau Daya Listrik is one of Subsidiary PT Krakatau Steel. In transmitting and distributing electric power, needed sometool such as a transformer. Observations that have been done on network 20k shown that given the power transformer in the network of 16.4 Mw while the received power by a transformer of 20.99 MW. The problem in this study is expected to determine the effect of a change in resistance of each tap into them, using the PSO algorithm is expected to minimize the loss of power flow flowing in the transformer. The results of these tests tap changer changes the resistance value is very influential on the flow of power loss, where the smaller the resistance value of the tap on the transformer, the greater the loss in power flow generated, in this test is the most optimal tap tap 2 on the value of income stream The minimum power of 0.043 pu. Key word : Tap changer, Power flow, PSO (Particle Swarm Optimization)