Harmonics Analysis of Input Current of 3-Phase PWM Rectifier
Main Authors: | Adjie, Alfin Prima, Hamid, Muhammad Imran |
---|---|
Format: | Article info application/pdf Journal |
Bahasa: | eng |
Terbitan: |
Electrical Engineering Dept, Engineering Faculty, Universitas Andalas
, 2021
|
Subjects: | |
Online Access: |
http://ajeeet.ft.unand.ac.id/index.php/ajeeet/article/view/6 http://ajeeet.ft.unand.ac.id/index.php/ajeeet/article/view/6/6 |
Daftar Isi:
- Rectifier is a non-linier load that causes harmonic distortion in the power system. Pulse-width modulation (PWM) method is an effective method in pressing the magnitude of harmonics in a rectifier application, it provides an almost sinusoidal input current. However, the variation of loads that supplied by a rectifier cause the harmonics that arise can still beyond the applicable standard. The amount of harmonics in the operating range of a rectifier need to be identified to determine the filter on the input side. In this research article, 3-phase PWM rectifier was designed with hysteresis current control technique using PSCAD software simulation. Harmonic compensation was carried out by applying an active filter based on P-Q theory to reduce the harmonic distortion that occurs in the input current, thus giving a low total harmonic distortion (THD) value. Based on the simulation, 3-phase PWM rectifier operation starting at a power level of 150 kW, giving a THD value above 5-10% by the increasing the amount of load supplied by the rectifier. The application of active filter based on the P-Q theory is able to compensate harmonics in the input current wave with a THD value below 5% in the rectifier operating range.