PENENTUAN KAPASITAS DAN KARAKTERISTIK MODUL PV PADA PERENCANAAN PEMBANGUNAN PLTS KOMUNAL DI DISTRIK OKABA
Main Authors: | Haryanto Sumbung, Frederik, Letsoin, Yohanes, Hardiantono, Damis |
---|---|
Format: | Article eJournal |
Bahasa: | ind |
Terbitan: |
, 2016
|
Subjects: | |
Online Access: |
https://zenodo.org/record/3516494 |
Daftar Isi:
- The capacity of the PV modules according to the Okaba District data is calculated on the assumption of need ideal daily power which is determined in two categories of operational time of the PLTS communal system that is the operating system 12 (twelve) hours. For a total of 12 hours of total consumer power of 45,258 Wh / day, the capacity of the PV array module is 15 kWp with a PV power module of 200 Wp with a total of 74 PV modules arranged in series 8 units and 8.07 parallel circuits. With a capacity of 15 kWp requires 72 batteries with 24 batteries connected in series as many as 3 groups connected in parallel. According to the daily light intensity of the Okaba District, the efficiency of the PV 200 Wp module is 2.76% meaning that with the 200 Wp PV module used in communal PLTS in the Okaba District is still not good / less efficient, it is better to use a PV module above 200 Wp to get good efficiency in accordance with the standard efficiency of PV modules