Energy Analysis for Air Conditioning System Using Fuzzy Logic Controller

Main Authors: Nasution, Henry; Universitas Bung Hatta (UBH), Universiti Teknologi Malaysia (UTM), Jamaluddin, Hishamuddin; Universiti Teknologi Malaysia (UTM), Mohd. Syeriff, Jamaluddin; Universiti Teknologi Malaysia (UTM)
Format: Article info application/pdf eJournal
Bahasa: eng
Terbitan: Universitas Ahmad Dahlan , 2011
Online Access: http://journal.uad.ac.id/index.php/TELKOMNIKA/article/view/680
http://journal.uad.ac.id/index.php/TELKOMNIKA/article/view/680/519
Daftar Isi:
  • Reducing energy consumption and to ensure thermal comfort are two important considerations for the designing an air conditioning system. An alternative approach to reduce energy consumption proposed in this study is to use a variable speed compressor. The control strategy will be proposed using the fuzzy logic controller (FLC). FLC was developed to imitate the performance of human expert operators by encoding their knowledge in the form of linguistic rules. The system is installed on a thermal environmental room with a data acquisition system to monitor the temperature of the room, coefficient of performance (COP), energy consumption and energy saving. The measurements taken during the two hour experimental periods at 5-minutes interval times for temperature setpoints of 20oC, 22oC and 24oC with internal heat loads 0, 500, 700 and 1000 W. The experimental results indicate that the proposed technique can save energy in comparison with On/Off and proportional-integral-derivative (PID) control.