Analysis of Transmission Lightning Arrester Locations Using Tflash
Main Authors: | Jambak, M. I.; Universitas Sriwijaya, Nawawi, Z.; Universitas Sriwijaya, Kurnia, R.F.; Universitas Sriwijaya, Buntat, Z.; Universiti Teknologi Malaysia, Sidik, M. A. B.; Universitas Sriwijaya, Arief, Y. Z.; Universiti Teknologi Malaysia, Wahab, A. A.; Tenaga Nasional Berhad, Ramli, Z.; Tenaga Nasional Berhad, Ramly, M. E.; Tenaga Nasional Berhad |
---|---|
Format: | Article info application/pdf eJournal |
Bahasa: | eng |
Terbitan: |
Universitas Ahmad Dahlan
, 2016
|
Subjects: | |
Online Access: |
http://journal.uad.ac.id/index.php/TELKOMNIKA/article/view/3792 http://journal.uad.ac.id/index.php/TELKOMNIKA/article/view/3792/2990 |
Daftar Isi:
- Tropical countries with extensive lightning activity, such as Malaysia, encounter numerous problems on their electrical transmission and distribution systems. Many overhead lines trip because of back flashover of lightning and shielding failures of the grounding system. To overcome the problem and improve transmission line performance, a detailed lightning study is required to analyse the corresponding lines and determine the best location for transmission line arrester (TLA) installation. We used TFlash to analyse a TLA installation on a 132-kV SSWW-BBST overhead transmission line system located in Selangor, Malaysia. Based on the results, the installation of the TLA at the optimum quantity and at appropriate towers have reduced the number of lines that trip.