Daftar Isi:
  • Administration Head Office (KPA) is one of the buildings contained in State Polytechnic of Sriwijaya.There are 3 floors which each floor has various activities every day as well as various load characteristics such as lighting load, cooling load / air conditioner (AC), electronic load and backup source in the form of socket. The operation of the load is not simultaneous so that its use of power will vary. To determine the use of electrical power in KPA then calculated load and current measurements to determine the load used. Measurements are done every Monday - Friday from 07.00 - 17.00 WIB since 13 - 24 March 2017. Based on current measurement results, theused power when the peak load condition is 110.030,8 Watt, the lowest load with the power of 57,427.7 Watt and the average load for two weeks is 77,557.93 WattHour. While the installed load is 258,467 Watts and the installed power capacity is 270,600 VA.