PENENTUAN TAHANAN PENTANAHAN PADA GARDU INDUK 70 KV/20 KV DI SEDUDUK PUTIH
Main Author: | Nasri, Satrian |
---|---|
Format: | Thesis NonPeerReviewed Book |
Bahasa: | eng |
Terbitan: |
, 2014
|
Subjects: | |
Online Access: |
http://eprints.polsri.ac.id/396/1/Cover.pdf http://eprints.polsri.ac.id/396/2/Bab%201.pdf http://eprints.polsri.ac.id/396/3/Bab%202.pdf http://eprints.polsri.ac.id/396/4/Bab%203.pdf http://eprints.polsri.ac.id/396/5/Bab%204.pdf http://eprints.polsri.ac.id/396/6/Bab%205.pdf http://eprints.polsri.ac.id/396/7/Daftar%20Pustaka.pdf http://eprints.polsri.ac.id/396/ |
Daftar Isi:
- Price low resistance of a grounding system is measured not yet guarantee that the earthing system is already good. This is because the possibility of measurements made improper. Making final report aims to determine the magnitude of the resistance value at the substation grounding Seduduk Putih. Proper grounding resistance measurements need to be done to check if the price of the grounding prisoners already qualified are allowed. Apart from the measurement data, the grounding resistance value can also be calculated manually or by using a particular application program. To find out the results of these calculations using the slope method, the four voltage method, and the method of intersection. The results of the calculation of the average slope method is R = 0.44 Ω. For the calculation of the average of the four voltage method is R = 0.3369 Ω. And the results of the calculation of the average intersection method is R = 0.45 Ω. Keywords:substation, grounding systems, the slope method, the four voltage method and the intersection method.