ANALISA EFISIENSI PEMBEBANAN JARINGAN DISTRIBUSI TEGANGAN MENENGAH PADA PENYULANG ONTA YANG DI SUPLAI DARI GI BUKIT SIGUNTANG
Main Author: | KHOIRUL, INSAN |
---|---|
Format: | Thesis NonPeerReviewed Book |
Bahasa: | eng |
Terbitan: |
, 2016
|
Subjects: | |
Online Access: |
http://eprints.polsri.ac.id/3797/1/File%20I.pdf http://eprints.polsri.ac.id/3797/2/File%20II.pdf http://eprints.polsri.ac.id/3797/3/File%20III.pdf http://eprints.polsri.ac.id/3797/4/File%20IV.pdf http://eprints.polsri.ac.id/3797/5/File%20V.pdf http://eprints.polsri.ac.id/3797/6/File%20VI.pdf http://eprints.polsri.ac.id/3797/7/DAFTAR%20PUSTAKA.pdf http://eprints.polsri.ac.id/3797/ |
Daftar Isi:
- To find the voltage value and losses of distribution network on Onta feeder,the author did the manual calculation and also ETAP 12.6.0 software calculation.The results of calculation from drop voltage and power losses using ETAP 12.6.0 was done by collecting datas of network length and current of load. Based on the manual calculation ,the highest efficiency on Onta feeder was obtained when it was at lowest load .It was about 97,28 % (daylight).Whereas the lowest efficiency for manual calculation obtained when it was at highest load .It was about 95,17 % (daylight).Based on ETAP simulink calculation , the highest efficiency on Onta feeder obtained when it was at lowest load .It was about 98,29% (daylight). Whereas the lowest efficiency for ETAP calculation was obtained when it was at highest load.It was about 96,67 % (daylight. So it was obtained the deviation (differences) between manual calculation and ETAP calculation .As the result to make the efficiency increase is changing the bigger size of cable .