ANALISA SETTING RELAY GANGGUAN TANAH PADA PENYULANG 20 kV di GARDU INDUK SEDUDUK PUTIH
Main Author: | Pratama, Muhammad Oktavian |
---|---|
Format: | Thesis NonPeerReviewed Book |
Bahasa: | eng |
Terbitan: |
, 2015
|
Subjects: | |
Online Access: |
http://eprints.polsri.ac.id/1752/1/Cover.pdf http://eprints.polsri.ac.id/1752/2/Bab%201.pdf http://eprints.polsri.ac.id/1752/3/Bab%202.pdf http://eprints.polsri.ac.id/1752/4/Bab%203.pdf http://eprints.polsri.ac.id/1752/5/Bab%204.pdf http://eprints.polsri.ac.id/1752/6/Bab%205.pdf http://eprints.polsri.ac.id/1752/7/DAFTAR%20PUSTAKA.pdf http://eprints.polsri.ac.id/1752/ |
Daftar Isi:
- Rele is one part of protection system that serves to detect disorder that occurs .Land rele disorder digunakna as detection disorder hyphen brief to ground in phase 1 which coordinated with over current relay ( ocr ) or cover behind automatic ( pbo , automatic circuit recloser ) . This research done by examining the suit rele disorder of ground , then calculate the hyphen in phase one brief to the ground each feeder connected to a busbar , counting a suit of the current and time. The results of research recommends rele a disorder of the ground with the suit is the smallest current isett = 26,58 ampere to penyulang pipit and the suit is the largest current isett = 28,00 ampere to penyulang beo .The suit all time rele have an average of tms 0.1 .Said the key: rele disorder land gfr ) , hyphen brief , setting the current Keywords: Ground Fault Relay (GFR), short circuit ,current setting.